EasyManua.ls Logo

Altronic DE-3000 - Cool-Down Screen

Altronic DE-3000
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DE-3000 IOI 7-17
All rights reserved © ALTRONIC, LLC 2017
24
PRESS
RESET
TIMERS ACTIVE
STATUS TIMERS ACTIVE
SPEED 1000 RPM
SUCTION 102.3 PSIA
DISCHARGE 200 PSIG
14.0
COOL-DOWN SCREEN
14.1 The cool-down mode enables the engine to enter a state before shutting down
where a number of sensors may normally fault low. Class B and C channels that
are configured for cool-down will not cause a fault during cool-down mode if
an input falls below the corresponding low safety setpoint (analog channels) or
switches out of its normal condition (discrete channels).
To enter cool-down mode, from the home screen, press the F2 key.
PRESS
F2
PRESS THE ENTER KEY
TO COOL-DOWN, OR
PRESS ESC TO EXIT
RUNNING
Pressing enter will start the cool-down timer and activate the cool-down chan-
nels. The status line on the home screen will display COOLDOWN xxx s; xxx
being the remaining cool-down time. Channels that are not programmed as cool-
down channels may still cause faults during this time.
PRESS
ENTER
STATUS COOLDOWN 1s
SPEED #1 1532 RPM
NOTUSED ---- ---
NOTUSED ---- ---
RUNNING
When the cool-down timer expires, the home screen status line will read FAULT
AL12 with the description, COOL-DOWN SHUTDOWN.
1
ST
FAULT
STATUS FAULT AL12
1st FAULT
COOL-DOWN SHUTDOWN
STATUS TIMERS ACTIVE
SPEED 1000 RPM
SUCTION 102.3 PSIA
DISCHARGE 200 PSIG

Table of Contents