CHAPTER 3: USING PROGRAMMING FUNCTIONS
UNIFLOW
®
4 PULSED HEAT CONTROL
3-28 990-908
SET RELEASE TIMER
Press the 3 key to bring up the SET
RELEASE TIMER
screen. You can use the
release timer to delay the initiation of a
new heating cycle after the thermode has
cooled down to the Cool temperature and
the release timer has expired.
Use the number or keys to select a
release timer value of 00 to 99 seconds.
< SET RELEASE TIMER >
SET RELEASE TIMER : 00
After edit Page to accept new value
Number Change, Adjust, Graph / Data
MAX. TEMPERATURE LIMIT
Press the 4 key to bring up the
MAX
TEMPERATURE LIMIT
screen. With this
screen, you may set the maximum
temperature required for an application
for the Main Thermocouple.
When entering reflow temperatures in
rofiles, the new reflow temperature
must be below the user set MAX
TEMPERATURE LIMIT.
< MAX TEMPERATURE LIMIT >
MAX TEMPERATURE LIMIT : 600
After edit Page to accept new value
Number Change, Adjust, Graph / Data
The default temperature of 600C is shown on the screen above. A maximum temperature up to 999C
can be entered. Use the keys to edit the value.
MAX. AUX TEMPERATURE LIMIT
Press the 5 key to bring up the MAX AUX
TEMPERATURE LIMIT
screen. With this
screen, you may set the maximum
temperature possible for the Auxiliary
Main Thermocouple. The default
temperature of 600C is shown on the
screen to the right. A maximum
temperature up to 999C can be entered.
Use the
keys to edit
< MAX AUX TEMPERATURE LIMIT >
MAX AUX TEMPERATURE LIMIT : 600
After edit Page to accept new value
Number Change, Adjust, Graph / Data
the value. The Control will abort the
process if the MAX AUX TEMPERATURE LIMIT is reached.