Sensor Default Settings | E-1
SERIES 2000 CONTROLLER
SETUP PARAMETERS
O2 PRODUCTS O2 PRODUCTS INCLUDE CLEAR AREAS ONLY
COMB. PRODUCTS COMB. PRODUCTS INCLUDE CLEAR AND SHADED AREAS
METHANE PRODUCTS METH. PRODUCTS INCLUDE CLEAR,SHADED,AND BORDERED AREAS
PARAMETER DEFAULT SETTINGS CUSTOMER SETTINGS
SENSOR CONFIGURE O2
CEM/O2, INSITU
WDG-IV, WDG-HPII
SENSOR CONFIGURE COMB WDG-IVC, WDG HPIIC
SENSOR CONFIGURE METHANE WDG-IVCM
SENSOR NODE ADDRESS 0
BAUD RATE 9600
ENABLE SERIAL ENABLED
COMBUSTIBLE TYPE HOTWIRE
COMBUSTIBLE TYPE RTD
COMBUSTIBLE SCALE PPM
PROCESS PRESSURE 0.00 PSIG
O2 SPAN GAS SETPOINT 20.90%
O2 ZERO GAS SETPOINT 2%
COMB SPAN GAS SETPOINT 1600 PPM
METHANE GAS SETPOINT 2.00%
AUTO CAL CYCLE TIME 8:00
AUTO CAL CYCLE FREQ 1 DAY
AUTO VERIFY CYCLE TIME 9:00
AUTO VERIFY CYCLE FREQ 1 DAY
AUTO CAL/VERIFY DAYS/HRS DAYS,DAYS
AUTO CAL ENABLE/DISABLE ENABLED
AUTO VER ENABLE/DISABLE ENABLED