EasyManua.ls Logo

Ampac ZoneSense Plus - Detector Removal Facility; Zone Circuit Wiring TB13 - 14; Monitored Alarms Outputs

Ampac ZoneSense Plus
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAN 2326-13
18
6.4.3 Detector Removal Facility
This facility allows for up to 20 detectors to be removed from their bases at any one me. If a detector
head is removed a fault will be indicated on that zone and all the other devices retain the ability to
iniate an alarm. This facility requires;
Schoky diodes having a voltage drop of 0.2 – 0.3 of a volt to be installed across L1 in and L1
out on the detector base. The limitaon on the number of heads that can be removed is a
direct result of the cumulave eect of the voltage drop across each diode. Diodes will not
be required if the head removal facility is not required.
The use and programming of a bipolar capacitor as the end of line (EOL) device.
6.5 Zone Circuit Wiring TB13 - 14
Zone circuit connecons are made directly to TB13 & TB14 on the Main Card and if screened cabling
is used the screen is terminated at the panel's chassis earth terminal.
Reminder 1: A maximum of 32 ZoneSense PLUS compable Opcal / Heat Detectors or Manual
Call Points can be ed to each circuit and mixed in any order.
Reminder 2: An End of Line Capacitor must be connected across the terminals of the last device
on each circuit. Unused Zones must have an End of Line capacitor ed at the panel.
L1 In
L1 Out
Earth
L2
-R
+
-
APOLLO SERIES 60 DIODE
BASE WIRING
The diode is used when the detector removal facility is utilised
L1 In
L1
Out
Earth
L2
-R
+
-
APOLLO STANDARD
BASE WIRING
Earth
L2
-R
EOL
L1 In
+
-
TB
13
&
14
MAIN
PCB
Figure 16: Typical Detector Wiring with Detector Removal Facility Diodes
6.6 Monitored Alarms Outputs
The panel has 4 dedicated individually monitored outputs terminated to TB4 which are;
Rated at 500mA @ 24VDC nominal;
Protected against short circuits;
Monitored for open and short circuit condions even when an output is acve. The
monitoring operates on a reverse voltage principal and will indicate a fault within 60 seconds.
Programming which zones will operate any of the outputs is done via the front Panel.

Table of Contents

Other manuals for Ampac ZoneSense Plus

Related product manuals