15.1 Procedure
The following tests are the minimum that should be performed when commissioning a system using
the ZoneSense PLUS Fire Alarm Control Panel. Supplements to these tests may be added by way of
aachments or notaon (using waterproof ink) to this documentaon. If supplements or tests are added
reference to them shall be made at an appropriate point on this document.
This Commissioning Record is to be completed in conjuncon with the:
➢ Operator’s manual;
➢ Installer’s statement(s);
➢ 'as-installed' drawings; and
➢ Detector test records,
The Record provides a complete descripon of the installed system and its tested performance at the
me of being commissioned.
15.2 System Information
Tick relevant box
1. Ensure that all detectors used in the system -
Are listed in the operator's manual;
Are compable with the installed AZF,
Do not exceed the permied number of detectors on each
circuit; and
Are installed in an environment for which they are suitable.
Check that the primary power source for the system has been
provided in accordance with wiring regulaons, and that the
isolang switch disconnects the acve conductors.
Check that the detector and the FACP locaons are in accordance
with the appropriate clauses of the code.
Measure each alarm zone circuit voltage, and ensure each is
within the equipment manufacturer's specicaons.
Insulaon resistance of all installaon wiring measured in
accordance with regulaons or similar approved method and
record the worst case result in the logbook.
Open circuit and short circuit the end of line device on each alarm
zone circuit, or conduct other appropriate tests to ensure that fault
and alarm condions are operang correctly on all alarm zone
facilies on other secons of the control and indicang equipment.