8 Internal Terminal Block Numbering Quick Reference
Terminal Block
TP Number
EN54
COMMUNICATIONS EXTERNAL
TB2/1
RS485 +
2
28
RS485 -
3
29
Shield
INPUTS
TB3/1
Common
2
25
Spare
3
26
Class Change
4
27
Alert
ZONES ( 24mA / Zone )
TB13/1
1
+ Zone 1
2
2
- Zone 1
3
3
+ Zone 2
4
4
- Zone 2
5
5
+ Zone 3
6
6
- Zone 3
7
7
+ Zone 4
8
8
- Zone 4
TB14/1
9
+ Zone 5
2
10
- Zone 5
3
11
+ Zone 6
4
12
- Zone 6
5
13
+ Zone 7
6
14
- Zone 7
7
15
+ Zone 8
8
16
- Zone 8
MONITORED OUTPUTS ( 500mA / O/p )
TB4/1
17
Alarm 1 +
2
18
Alarm 1 -
3
19
Alarm 2 +
4
20
Alarm 2 -
5
21
Alarm 3 +
6
22
Alarm 3 -
7
23
Alarm 4 +
8
24
Alarm 4 -
MODIFIED OPEN COLLECTOR OUTPUTS ( 25 mA /O/P )
TB5/1
25
Fire +
2
26
Fire -
3
27
Fault +
4
28
Fault -
OUTPUTS VOLT FREE RELAY ( 1A @ 30VDC )
5
29
NO Alarm
6
30
C Alarm
7
31
NC Alarm
8
32
NO Fault
9
33
C Fault
10
34
NC Fault
TB12/1
35
Aux 24VDC + (Mon 500mA)
2
36
Aux 24VDC –
3
37
Reset 3sec 24VDC 100mA max pulse