GT300 Installation
IMGT30017EN 29
Model Supply Main Fuses
1
Fuses type) Cables section Terminals
Max torque
Max Line Short
Circuit Current
[A] (UL) AWG mm
2
Nm lbf ft kA
F=Three-phase supply voltage 380V, 415V, 440V, 460V, 480V / Y=510-650V
DC
±10%
SVGT200F AC 300x3 FWH-350 2x2/0 2x95 3x2-M10 22,5 16.59 18
SVGT200Y DC 450x2 FWP-450A 2x2/0 2x95 2x2-M10 22,5 16.59 18
SVGT250F AC 350x3 FWH-400A 2x3/0 2x95 3x2-M10 22,5 16.59 18
SVGT250Y DC 600x2 FWP-600A 2x3/0 2x95 2x2-M10 22,5 16.59 18
SVGT292F AC 500x3 FWH-500A 3x3/0 3x95 3x2-M10 22,5 16.59 18
SVGT292Y DC 800x2 FWP-800A 3x3/0 3x95 2x2-M10 22,5 16.59 18
SVGT340F AC 600x3 FWH-700A 3x4/0 3x120 3x2-M10 22,5 16.59 30
SVGT340Y DC 900x2 FWP-900A 3x4/0 3x120 2x2-M10 22,5 16.59 30
SVGT420F AC 770x3 FWH-700A 4x4/0 4x120 3x2-M10 22,5 16.59 30
SVGT420Y DC 1000x2 FWP-1000A 4x4/0 4x120 2x2-M10 22,5 16.59 30
SVGT470F AC 800x3 FWH-800A 4x4/0 4x120 3x2-M10 22,5 16.59 30
SVGT470Y DC 1000x2 FWP-1000A 4x4/0 4x120 2x2-M10 22,5 16.59 30
SVGT520F AC 850X3 FWP-900A na (2X195)X2 (3x2-M10) X2 22,5 16.59 30
SVGT520Y DC 700X4 FWP-700A na (3X95)X2 (2x2-M10) X2 22,5 16.59 30
SVGT580F AC 1000X3 FWP-1000A na (3X95)X2 (3x2-M10) X2 22,5 16.59 42
SVGT580Y DC 800x4 FWP-800A na 3X(95)X2 (2x2-M10) X2 22,5 16.59 42
SVGT670F AC 1200X3 FWP-1200A na (3X120)X2 (3x2-M10) X2 22,5 16.59 42
SVGT670Y DC 900x4 FWP-900A na (3X120)X2 (2x2-M10) X2 22,5 16.59 42
SVGT780F AC 1400x3 FWP-1400A na (4x120)X2 (3x2-M10) X2 22,5 16.59 85
SVGT780Y DC 1000x4 FWP-1000A na (4x120)X2 (2x2-M10) X2 22,5 16.59 85
SVGT940M AC 800x6 FWH-800A na (4x120)X2 (3x2-M10) X2 22,5 16.59 85
SVGT940Y DC 1000x4 FWP-1000A na (4x120)X2 (2x2-M10) X2 22,5 16.59 85
K=Three-phase supply voltage 525V, 550V, 575V, 600V, 660V, 690V /J=705-930V
DC
-10% +15%
SVGT105K AC 125X3 FWP-125A 2 35 3x1-M8 10 7.37 10
SVGT105J DC 150X2 2 35 2x1-M8 10 7.37 10
SVGT130K AC 150X3 FWP-150A 1/0 50 3x1-M8 10 7.37 10
SVGT130J DC 175X2 1/0 50 2x1-M8 10 7.37 10
SVGT170K AC 175X3 FWP-300A 3/0 95 3x1-M8 10 7.37 10
SVGT170J DC 200X2 3/0 95 2x1-M8 10 7.37 10
SVGT200K AC 200X3 FWP-200A 4/0 120 3x1-M10 22,5 16.59 10
SVGT200J DC 250x2 4/0 120 2x1-M10 22,5 16.59 18
SVGT260K AC 250X3 FWP-250A 2x2/0 2x50 3x1-M10 22,5 16.59 10
SVGT260J DC 300X2 2x2/0 2x95 2x1-M10 22,5 16.59 18
SVGT320K AC 300X3 FWP-350A 2x2/0 2x95 3x1-M10 22,5 16.59 10
SVGT320J DC 400X2 2x2/0 2x95 2x1-M10 22,5 16.59 18
SVGT390K AC 450X3 FWP-500A 2x4/0 2x120 3x1-M10 22,5 16.59 18
SVGT390J DC 450X2 2x4/0 2x120 2x1-M10 22,5 16.59 18
SVGT480K AC 500X3 FWP-500A 3x4/0 3x95 3x1-M10 22,5 16.59 18
SVGT480J DC 600X2 3x4/0 3x120 2x1-M10 22,5 16.59 18
SVGT521K AC 850X3 FWP-900A (2x2/0)x2 (50x2)x2 3x1-M10 22,5 16.59 18
SVGT521J DC 700X2 (2x2/0)x2 (95x2)x2 2x1-M10 22,5 16.59 18
SVGT640K AC 1000X3 FWP-1000A (2x2/0)x2 (95x2)x2 (3x1-M10)x2 22,5 16.59 30
SVGT640J DC 800x4 (2x2/0)x2 (95x2)x2 (2x1-M10)x2 22,5 16.59 30
SVGT780K AC 1200X2 FWP-1200A (2x4/0)x2 (120x2)x2 (3x1-M10)x2 22,5 16.59 30
SVGT780J DC 900x4 (2x4/0)x2 (120x2)x2 (2x1-M10)x2 22,5 16.59 30
SVGT960K AC 1400x3 FWP-1400A (3x4/0)x2 (3x95)x2 (3x1-M10)x2 22,5 16.59 42
SVGT960J DC 1000x4 3x4/0)x2 (3x120)x2 (2x1-M10)x2 22,5 16.59 42
Cable sections shown in the tables are guidelines only. Refer to local regulations concerning cables for correct
sizing. A larger cable section may be required in some cases to prevent too high of a voltage drop.
1
Standard gG fuses with current rating: 1.3 times GT3000 rated current for AC power supply can be used on CE market.
WARNING