Pxxxx/EN SS/C11
Page 8/10 Safety Section
7. TECHNICAL SPECIFICATIONS FOR SAFETY
7.1 Protective fuse rating
The recommended maximum rating of the external protective fuse for equipments is 16A,
high rupture capacity (HRC) Red Spot type NIT, or TIA, or equivalent, unless otherwise
stated in the technical data section of the equipment documentation. The protective fuse
should be located as close to the unit as possible.
DANGER - CTS MUST NOT BE FUSED SINCE OPEN CIRCUITING THEM
MAY PRODUCE LETHAL HAZARDOUS VOLTAGES.
7.2 Protective Class:
IEC 61010-1: 2001
EN 61010-1: 2001
Class I (unless otherwise specified in the equipment
documentation). This equipment requires a protective
conductor (earth) connection to ensure user safety.
7.3 Installation Category:
IEC 61010-1: 2001
EN 61010-1: 2001
Installation Category III (Overvoltage Category III):
Distribution level, fixed installation.
Equipment in this category is qualification tested at
5 kV peak, 1.2/50 µs, 500 Ω, 0.5 J, between all
supply circuits and earth and also between
independent circuits
7.4 Environment:
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be mounted in a specific cabinet or housing which will
enable it to meet the requirements of IEC 60529 with the classification of degree of
protection IP54 (dust and splashing water protected).
Pollution Degree – Pollution
Degree 2
Altitude – operation up to 2000 m
IEC 61010-1: 2001
EN 61010-1: 2001
Compliance is demonstrated by reference to safety
standards.