45-Door limit-switch fault: If a door limit switch is assigned as "connected" in P0013 and/or P0020 parameters,
but does not function as expected, this error is raised.
- Either the parameter should be selected “not used” or the limit-switch connection should be done correctly.
47-Brake resistor overheated: The temperature of brake resistor is estimated depending on the change of voltage
in the brake resistor. If the calculated value exceeds a certain value, this error occurs.
- Check that brake resistor is chosen suitable for Arcode.
- For the ventilation of brake resistor to be good, around the brake resistor should be empty, and open for ventilation.
48-Heatsink overheated: If IPM temperature exceeds the value of “P0774:heatsink overheat error threshold”, it
gives this error.
- Check that the fans are working well.
- Be sure that ventilation of control panel is good.
49-External error (XER1) signal activated: When this is activated, it stops the system immediately.
- Check that if the assigned input XER1 has signal or not. After signal position turns to OFF, within 5 seconds it turns
to normal operation.
50-External error (XER2) signal activated: When this is activated, it stops the system at the nearest floor
level.
- Check that if the assigned input XER2 has signal or not. After signal position turns to OFF, within 5 seconds it turns
to normal operation.
51-External blocking signal (XBL1) activated: When this is activated, it stops the system immediately and
blocked.
- Check that if the assigned input XBL1 has signal or not. After signal position turns to OFF, it requires either a reset
operation or turning the hand terminal to “inspection” and “normal” again, then it turns to normal operation.
52-External blocking signal (XBL2) activated: When this is activated, it stops the system at the nearest floor
level and blocked.
- Check that if the assigned input XBL2 has signal or not. After signal position turns to OFF, it requires either a reset
operation or turning the hand terminal to “inspection” and “normal” again, then it turns to normal operation.
53- Encoder direction is wrong: Change the encoder direction from the menu. Auto-tune must be done again
when the encoder direction is changed for gearless machine.
54- OGD Error: A shaky starting occurs when the anti roll back value is entered too high. This error may be faced
with in this case. Decrease gains of anti roll back.
55- Contactor dropped: When the movements starts, during movement, if 100 signal is cut for 100 milliseconds,
this error is received. The signal 100 that normally passes through open contacts of KPA, KPB and KFR contactors
comes to ARCODE’s EN input. There must be signal 100 in EN input when all the contactors are activated.
56- 817&818 cut at the same time: Both 817 and 818 signals are cut at the same time for 0,5 seconds, it gives
this error.
- Check 817,818 signals and their magnetic sensors.
- Check the power supply of magnetic sensors.