Arkel Elektrik Elektronik San. ve Tic. A.Ş. www.arkel.com.tr
ARKEL 70 ARCODE
95-Manual rescue (SEV key): If “P0810 Acceptance test tools” parameter is OFF and “MEM” signal is ON, this
error occurs.
96-UPS failed on test: If UPS test couldn’t be performed, it gives this error.
- Check the batteries.
Note: This is a permanent error. In order to get rid of the permanent error case, look at Appendix-3.
97-Direction change limit reached: "(P0964) Direction change count limit" is set to a non-zero value and the
direction change counter has exceeded this value.
- This function is usually used to limit the usage of plastic ropes according to their lifetime. After changing the ropes,
set (P0964) to the next desired limit value.
Note: This is a permanent error. In order to get rid of the permanent error case, look at Appendix-3.
98- One of critical devices is offline: During normal operation, if connection with a critical device is lost, the
controller raises error. (Triggering of this error may take about 20 seconds) For ex: Photocell (FSLA) input is assigned to
one of the programmable inputs of IBC board, and if there is a problem about the communication with IBC and main
controller, this error is triggered in normal operation. The critical programmable inputs are shown with red color in the
programable input list.
-This error is about EN81-20 norms. Not to receive this error during installation, you should set the “Operation mode”
parameter as “Installation mode”.