ARKEL 62 ARCODE
ERROR CODES - POSSIBLE REASONS AND SOLUTIONS
01- Couldn’t read parameters. Checksum wrong: If Eeprom is empty or checksum is faulty, it gives this
error. Try to restart system. If it doesn’t solve, get contact to Arkel support.
02-Couldn’t write parameters. Verify error: If it couldn’t write the parameters or statistics to Eeprom, it
gives this error. Try to restart system. If it doesn’t solve, get contact to Arkel support.
03-Parameters were written with a newer version. Some parameters will be lost: If the system is
updated to an older version, and if the functions in new version don’t exist in the updated version, the values in the first
version (before update) is cleared.
04- No connection with ENCA board: If ARCODE can not communicate with ENCA board more than 1
second, it gives this error.
- When this error is received, encoder links must be controlled. Encoder link can be wrong or there may be a problem
with encoder feed.
- The flat cable between Arcode and ENCA should be checked.
- Encoder type and motor type parameters should be checked.
05-DIP-switch configuration wrong or could not be read: When dipswitches are adjusted in a wrong way,
it gives this error.
- You can get contact to Arkel support.
06- One of encoder channels disconnected: This error occurs when there is no info from ENCA board for 1
second.
- The flat cable between Arcode and ENCA, and encoder connections should be checked.
07- Current was over driver limit: If the motor current exceeds over 200% of max.current of IPM module, it
gives this error.
- Arcode capacity should be suitable with motor.
- The car shoes may be too tight or the motor brake may not open fully.
- For geared machine ‘nominal slip frequency’ parameter might be entered wrong.
- ‘Noload current’ parameter should be checked.
08-Current was near driver limit continuously: If the motor current exceeds over 250% of max.current of
IPM modüle for 6 seconds, it gives this error.
- Be sure that load balance is completed correctly.
- Check the machine brake is being opened completely.
- Check the ‘nominal slip frequency’ and ‘noload current’ parameters in asynchronous machines.