5.5.8 Nurse and bed functionality
Solution 1
Connect a bridge between 3 and 7 on the secondary EXU-SI.
Use any impulse on primary to open primary door.
Use Open/Close impulse on secondary to open both doors.
Solution 2
Connect a bridge between 3 and 7 on the secondary EXU-SI.
Set dip switch PAG on primary board to ON.
Use any impulse on primary to open primary door.
Push secondary door manually and it will open up automatically and stay open until primary door
is closing.
Active in Program Selection OFF, EXIT, AUTO and OPEN.
Solution 3
Connect a 1/0 switch between 3 and 7 on the secondary EXU-SI.
Switch in pos. 1, impulses on primary will open only primary door.
Switch in pos. 0, impulses on primary will open both doors.
Note! How to connect KILL input is determined by chosen parameter group at the secondary, be
sure that chosen group has KILL-impulse configuration Normally Open. If KILL has to be Normally
Closed, terminal 3 and 7 should be disconnected instead of connected.
1009728-en-9.0Issue 2021-02-2418