3
Do not use means to accelerate the defrosng process or to clean, other than those
recommended by the manufacturer.
The appliance shall be stored in a room without connuously operang ignion
sources (for example: open ames, an operang gas appliance or an operang
electric heater).
Do not pierce or burn.
Be aware that R32 refrigerant may not contain an odour.
INSTALLATION AND MAINTENANCE
Our products may only be assembled and installed in pools compliant with
standards IEC/HD 60364-7-702 and required naonal rules. The installaon should
follow standard IEC/HD 60364-7-702 and required naonal rules for swimming
pools. Consult your local dealer for more informaon.
The appliance may not be installed close to combusble materials, or the air duct
inlet of an adjacent building.
During installaon, troubleshoong and maintenance, pipes may not be used as
steps: the pipe could break under the weight, spilling coolant and possibly causing
serious burns.
When servicing the appliance, the composion and state of the heat transfer uid
must be checked, as well as the absence of any traces of coolant.
During the appliance's annual sealing test in accordance with applicable legislaon,
the high and low pressure switches must be checked to ensure that they are
securely fastened to the cooling circuit and that they cut o the electrical circuit
when tripped.
During maintenance work, ensure there are no traces of corrosion or oil around
the cooling components.
Before beginning work on the cooling circuit, stop the appliance and wait for a few
minutes before ng the temperature and pressure sensors. Some elements such
as the compressor and piping may reach temperatures in excess of 100°C and high
pressures with the consequent risk of severe burns.
TROUBLESHOOTING
All brazing must be carried out by qualied brazers.
Replacement pipes must always be made of copper in compliance with standard
NF EN 12735-1.
Leak detecon; pressure test:
- never use oxygen or dry air (risk of re or explosion)
- use dry nitrogen or the mixture of nitrogen and refrigerant indicated on the
informaon plate,
- the test pressure for both the high and low pressure circuits must not exceed 42
bar in cases where pressure gauges are connected to the appliance.
The high pressure circuit pipes are made of copper and have a diameter equal to or
greater than 1’’5/8. A cercate as indicated in §2.1 in compliance with standard
NF EN 10204 must be requested from the supplier and led in the installaon's
technical le.
Technical data relave to the safety requirements of the various applicable direcves
are indicated on the informaon plate. All this informaon must be recorded in the
appliance's installaon manual, which must be kept in its technical le: model,
code, serial number, maximum and minimum OT, OP, year of manufacture, CE
marking, manufacturers address, coolant and weight, electrical parameters,
thermo-dynamic and acousc performance.
LABELLING
Equipment shall be labelled stang that it has been decommissioned and emped
of refrigerant.
The label shall be dated and signed.
For appliances containing ammable refrigerants, ensure that there are labels on
the equipment stang the equipment contains ammable refrigerant.