- 64 -
6.4.7 Checking intercooler relief valves
The valves should open at a pressure as specified in
the chapter Technical specifications.
If the valves open too soon: remove a washer, if
installed, between valve seat (4) and housing (1) or
add a washer between spring (2) and housing.
If the valves open too late: remove a washer, if
installed, between spring and housing or add a washer
between valve seat and housing.
6.4.8 Battery care
If the battery is still dry, it must be activated as
described in section 6.4.8.2.
The battery must be in operation within 2 months
from being activated; if not, it needs to be recharged
first.
6.4.8.1 Electrolyte
Electrolyte in batteries is a sulphuric acid solution in
distilled water.
The solution must be made up before being
introduced into the battery.
6.4.8.2 Activating a dry-charged battery
– Take out the battery.
– Battery and electrolyte must be at equal
temperature above 10°C.
– Remove cover and/or plug from each cell.
– Fill each cell with electrolyte until the level
reaches 10 to 15 mm above the plates, or reaches
the level marked on the battery.
Test the two intercooler relief valves
(1), which are fitted on the MP air
inlet pipe, statically on a compressed
air line at least once a year.
1 Valve housing
2Spring
3Valve
4Valve seat
5 Washer, copper
1
2
3
4
5
Before handling batteries, read the
relevant safety precautions and act
accordingly.
Read the safety instructions
carefully.