9. Electrical connection Work on the electrical system or equipment must only be
carried out by a skilled electrician himself or by specially
instructed personnel under the control and supervision of
such an electrician and in accordance with the applicable
electrical engineering rules.
9.1 Connection with AUMA plug/ socket connector
.
Check whether type of current, supply voltage and frequency correspond
to motor data (refer to name plate at motor).
.
Loosen bolts (50.01) (figure G-1) and remove plug cover.
.
Loosen screws (51.01) and remove socket carrier (51.0) from plug cover
(50.0).
.
Insert cable glands suitable for connecting cables.
(The enclosure protection stated on the name plate is only ensured if
suitable cable glands are used).
.
Seal cable entries which are not used with suitable plugs.
.
Connect cables according to order related wiring diagram.
The wiring diagram applicable to the actuator is attached to the
handwheel in a weather-proof bag, together with the operation
instructions. In case the wiring diagram is not available, it can be obtained
from AUMA (state commission no., refer to name plate) or downloaded
directly from the Internet (www.auma.com).
A special parking frame (figure G-2) for protection against touching the bare
contacts and against environmental influences is available.
11
Multi-turn actuators SA 07.1 – SA 16.1
Operation instructions with actuator controls AMB 01.1/AMB 02.1
Figure G-1: Connection
50.0
50.01
51.0
51.01
Bild G-2: Parking frame (accessory)
Parking frame
Technical data Protective earth Control pins
Contacts max. 1 (leading contact) 50 pins/sockets
Designation according to VDE 1 to 50
Voltage max. – 250 V
Current max. –
16 A
Type of customer connection Screw for ring lug Screws
Cross section max. 6 mm
2
2.5 mm
2
Material: Pin/socket carrier
Polyamide Polyamide
Contacts
Brass (Ms)
Brass, tin plated or gold plated (option)
Table 5: Technical data AUMA plug/socket connector