19.3 Push-to-run operation or self-retaining in selector switch position LOCAL
Push-to-run operation or self-retaining is set in the factory.
A change at a later date is only possible by cutting the link B3
(see figure R-2).
.
Remove local controls (figure R-1). The signal and control board is located
under the local controls (figure R-2).
Link cut: Push-to-run operation LOCAL.
Link closed: Self-retaining LOCAL.
19.4 Push-to-run operation or self-retaining in selector switch position REMOTE
Push-to-run operation or self-retaining is set in the factory.
If the operation mode is to be changed at a later date:
.
Loosen the three screws (1-3) and remove signal and control board
(figure R-2), but do not interrupt plug-in connections.
.
Move red plug-in link (figure S) on wiring board.
.
Fit signal and control board (figure R-2) again.
19.5 Fitting the local controls
.
Clean sealing faces of housing and cover
.
Check whether O-ring is in good condition.
.
Apply a thin film of non-acidic grease to the sealing faces.
.
Place local controls and fasten the bolts evenly crosswise.
24
Multi-turn actuators SA 07.1 – SA 16.1
with actuator controls AMB 01.1/AMB 02.1 Operation instructions
Plug-in link on B1 Self-retaining REMOTE
B2
B1
Push-to-run operation REMOTE
Plug-in link on B2 (Maintained contact REMOTE)
Selbsth.Fern
Puls contact
B1
B2
Dauerbefehl Fern
Maintained contact
Figure S: Wiring board
Plug-in link