Electronic control unit
Magnetic limit and torque transmitter (MWG)
Turns per stroke: 1 to 500 (standard) or 10 to 5,000 (option)
Non-Intrusive setting
Via actuator controlsPosition feedback signal
Via actuator controlsTorque feedback signal
Continuous self-adjusting indication with symbols OPEN and CLOSEDMechanical position indicator
Blinking signal via actuator controlsRunning indication
Resistance type heater with 5 W, 24 V ACHeater in switch compartment
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
2 000 m above sea level
> 2,000 m above sea level on request
Installation altitude
Refer to actuator name plateAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
IP68 with AUMA 3-phase AC motor
Terminal compartment additionally sealed against interior of actuator (double sealed)
Enclosure protection according to
EN 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:
Depth of water: maximum 8 m head of water
Duration of continuous immersion in water: Max. 96 hours
Up to 10 operations during continuous immersion
Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator controls name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according to IEC
60664-1
2 g, between 10 and 200 Hz (AUMA NORM ), 1g, 10 to 200 Hz (for actuators with AMExC or ACExC
actuator controls)
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:Corrosion protection
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
KX-G: Same as KX, however aluminium-free version (outer parts)
Options:
Double layer powder coating
Two-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Available colours on requestOption:
AUMA multi-turn actuators meet or exceed the lifetime requirements of EN 15714-2. Detailed information
can be provided on request.
Lifetime
< 72 dB (A)Noise level
Further information
ATEX Directive 2014/34/EU
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RED Directive 2014/53/EU
EU Directives
86
SAEx 07.2 SAEx 16.2 / SAREx 07.2 SAREx 16.2 Control unit: electronic (MWG)
Technical data ACExC 01.2 Non-Intrusive Profinet

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SAEx Series and is the answer not in the manual?

AUMA SAEx Series Specifications

General IconGeneral
Explosion protectionATEX, IECEx
Ingress protectionIP66 / IP68
Communication interfacesModbus, Foundation Fieldbus
DisplayLCD
Control Signal4-20 mA
Type of controllerElectric actuator controller

Related product manuals