Commands and signals of the Profinet interface
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, enable local
controls, Interlock OPEN/CLOSE, PVST
Process representation output
(command signals)
End positions OPEN, CLOSED
Actual position value
Actual torque value, requires MWG in actuator
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switches OPEN, CLOSED
Limit switches OPEN, CLOSED
Manual operation by handwheel or via local controls
Analogue (2) and digital (4) customer inputs
Process representation input
(feedback signals)
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
Process representation input
(fault signals)
The behaviour of the actuator is programmable:
Stop in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
Execute last received operation command
Behaviour on loss of communication
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
2 000 m above sea level
> 2,000 m above sea level, on request
Installation altitude
Refer to name plate of actuator controlsAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
IP68
Terminal compartment additionally sealed against interior of actuator controls (double sealed)
Enclosure protection according to
EN 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:
Depth of water: Maximum 8 m head of water
Duration of continuous immersion in water: Maximum 96 hours
Up to 10 operations during continuous immersion
Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator controls name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according to IEC
60664-1
1 g, from 10 Hz to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. (Not valid in combination with gearboxes)
Vibration resistance according to
IEC 60068-2-6
Suitable for use in areas with high salinity, almost permanent condensation, and
high pollution.
KSStandard:Corrosion protection
Suitable for use in areas with extremely high salinity, permanent condensation,
and high pollution.
KXOption:
Double layer powder coating
Two-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Available colours on requestOption:
91
SAEx 07.2 SAEx 16.2 / SAREx 07.2 SAREx 16.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profinet Technical data

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SAEx Series and is the answer not in the manual?

AUMA SAEx Series Specifications

General IconGeneral
Explosion protectionATEX, IECEx
Ingress protectionIP66 / IP68
Communication interfacesModbus, Foundation Fieldbus
DisplayLCD
Control Signal4-20 mA
Type of controllerElectric actuator controller

Related product manuals