Change settings:
11.
Press .
➥
Display indicates:
MODBUS 1 M1F1
VIEW
EDIT
12.
Press .
➥
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
13. Enter password:
→
Press 4 x = 0000 (default factory password).
➥
Display indicates:
EDIT M1F11
BAUDRATE
PARITY
CONNECT-CONTROL TIME
14.
Use to select BAUDRATE, PARITY or SLAVEADDRESS and confirm se-
lection with .
➥
Display shows the selected value. Example SLAVEADDRESS:
EDIT M1F14
SLAVEADDRESS
1
:EDIT C:ESC
15.
Press again to enter the edit mode.
➥
Display indicates:
EDIT M1F14
SLAVEADDRESS
1
:EDIT :OK C:ESC
16. Set new value:
→
Press .
52
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU