Chapter 3: Configuration and Parameters
Page 3–41Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
parameTer deTails – “advanCed” menu of parameTers (ConTinued)
P8.21 – Main Board Trip Hold. Reg. Type:
Description:
Read/Write
Detects if an unexpected event has occurred during the Main Board operation.
Range: Modbus Decimal Value: Default (decimal):
• Off : Main Board trip disabled.
• On : Main Board trip enabled.
• 0
• 1 • On (1)
Modbus Address: Modbus Format:
53800 ( D228 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → Main Board Trip
P8.22 – Keypad Trip Hold. Reg. Type:
Description:
Read/Write
Detects if an unexpected event has occurred during the Touchscreen operation.
Range: Modbus Decimal Value: Default (decimal):
• Off : Keypad Trip disabled.
• On : Keypad Trip enabled.
• 0
• 1
• OFF (0)
Modbus Address: Modbus Format:
53798 ( D226 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → Keypad Trip
P8.23– Logging Trip Hold. Reg. Type:
Description:
Read/Write
Detects if the logging to the internal SD card has failed to operate normally.
Range: Modbus Decimal Value: Default (decimal):
• Off : Logging trip disabled.
• On : Logging trip enabled.
• 0
• 1
• OFF (0)
Modbus Address: Modbus Format:
53799 ( D227 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → Logging Trip
P8.24 – Input Side Phase Loss Hold. Reg. Type:
Description:
Read/Write
Detects if there is a disconnection between the SR55 input and supply when motor is running.
Range: Modbus Decimal Value: Default (decimal):
• Off : The SR55 will attempt to run, although the operation may
be erratic. Operating in this mode for prolonged periods may
result in SCR failure.
• On : Trips if there is a disconnection between the input side of the
SR55 and the supply when the motor is running.
• 0
• 1
• On (1)
Modbus Address: Modbus Format:
53762 ( D202 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Trip Settings → Input Side Phase Loss