Page 3–22 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
advanCed” menu of parameTers
P1.0 – Save Parameters Hold. Reg. Type:
Description:
Read/Write
Saves all Read/Write parameters to non-volatile memory.
Note: This does not save the parameters to an external USB drive.
Range: Modbus Decimal Value: Default (decimal):
No : Parameters remain unchanged.
Yes : Parameters are written.
0
1
No (0)
Modbus Address: Modbus Format:
Touchscreen Menu Path:
advanCedauTomaTiC seTTings” parameTers
P2.0 – Automatic Pedestal Hold. Reg. Type:
Description:
Read/Write
Automatically controls the starting torque by adjusting the start voltage.
Range: Modbus Decimal Value: Default (decimal):
Off : The initial torque is defined by the “Start Pedestal.
On : The initial torque is increased until the motor starts to
rotate at a moderate speed.
0
1
Off (0)
Modbus Address: Modbus Format:
19840 ( 4D80 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Automatic Settings → Automatic Pedestal
P2.1 – Automatic Ramp Hold. Reg. Type:
Description:
Read/Write
Automatically controls the torque applied to the motor during the soft start by automatically
adjusting “Start Time” and “Current Limit.
Range: Modbus Decimal Value: Default (decimal):
Off : The ramp time depends on the “Start Time” and “Current
Limit.
On : The torque is adjusted to suit the load.
0
1
Off (0)
Modbus Address: Modbus Format:
20352 ( 4F80 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Automatic Settings → Automatic Ramp
P2.2 – Automatic End Start (1) Hold. Reg. Type:
Description:
Read/Write
Automatically controls the time taken for the motor to start.
Range: Modbus Decimal Value: Default (decimal):
Off : The ramp time depends on the “Start Time” and “Current
Limit.
On : The ramp time is shortened if the motor is at speed before
the end of the “Start Time.
0
1
Off (0)
Modbus Address: Modbus Format:
19968 ( 4E00 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Advanced → Automatic Settings → Automatic End Start (1)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals