Chapter 3: Configuration and Parameters
Page 3–15Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
pARAmeTeR deTAIls
This section describes the individual parameters and the functions that they perform.
SR55 parameters are defined as holding type registers.
parameTers noT Configurable Through TouChsCreen menu
These parameters are configurable only through network communications.
parameTers assoCiaTed WiTh digiTal inpuTs
P0.0 – Start/Stop (Digital Input Control Command Function) Hold. Reg. Type:
Description:
Read/Write
Starts or Stops the SR55.
• To map to digital input, refer to P10.2, P10.4, P10.6.
Range: Modbus Decimal Value: Default (decimal):
• Off : Stops or Soft Stops the SR55.
• On : Starts the SR55.
• 0
• 1
• Off (0)
Modbus Address: Modbus Format:
17920 ( 4600 hex ) 16-bit unsigned
Touchscreen Menu Path:
none
P0.1 – Freeze Ramp (Digital Input Control Command Function) Hold. Reg. Type:
Description:
Read/Write
If set to On, this parameter will hold the Start Ramp even if “Current I
rms
” is less than the
“Current Limit Level.”
• To map to digital input, refer to P10.2, P10.4, P10.6.
Range: Modbus Decimal Value: Default (decimal):
• Off : The Soft Start Ramp is not held and the SR55 will start in
the time set.
• On : The Soft Start Ramp is held and the SR55 will take longer
than the time set to start.
• 0
• 1
• Off (0)
Modbus Address: Modbus Format:
18240 ( 4740 hex ) 16-bit unsigned
Touchscreen Menu Path:
none
P0.2 – Reset (Digital Input Control Command Function) Hold. Reg. Type:
Description:
Read/Write
To reset pulse high and then low when resetting using communications.
• If using the touchscreen, the Start button will change to a Reset button during a fault condition.
• Clear the fault and press Reset.
• To map to digital input, refer to P10.2, P10.4, P10.6.
Range: Modbus Decimal Value: Default (decimal):
• Off : The final state required for a reset.
• On : The initial state required for a reset.
• 0
• 1
• Off (0)
Modbus Address: Modbus Format:
18368 ( 47C0 hex ) 16-bit unsigned
Touchscreen Menu Path:
none