EasyManua.ls Logo

Automation Direct Stellar SR55 Series - Trip Code Descriptions

Automation Direct Stellar SR55 Series
202 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 3–84 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
TRIp code descRIpTIoNs
Trip Codes (from Trip Log)
Number & Name Description
101
Input Side Phase
Loss
Phase L1 missing at the instant of start up�
The L1 phase is either missing or at a very low level�
Check all incoming connections�
If a main contactor is being controlled by a digital output set to “Running,” check that
“Contactor Delay” (under “Start Settings”) is sufficient�
102
Input Side Phase
Loss
Phase L2 missing at the instant of start up�
The L2 phase is either missing or at a very low level�
Check all incoming connections�
If a main contactor is being controlled by a digital output set to “Running,” check that
“Contactor Delay” (under “Start Settings”) is sufficient�
103
Input Side Phase
Loss
Phase L3 missing at the instant of start up�
The L3 phase is either missing or at a very low level�
Check all incoming connections�
If a main contactor is being controlled by a digital output set to “Running,” check that
“Contactor Delay” (under “Start Settings”) is sufficient�
104 - 117
Input Side Phase
Loss
Any or all phases missing when the motor is being controlled (running)�
L1, L2, or L3 are missing or at a very low level�
Check all incoming connections�
Check any fuses/breakers incorporated in the power circuit�
201
Maximum
Temperature
Exceeded
Internal heatsink temperature has exceeded 80°C�
It is possible the SR55 is operating outside specified limits�
Check enclosure ventilation and airflow around the SR55�
If the unit trips immediately, the internal temperature sensor could be faulty
208
Thermal Sensor Trip
Thermal sensor failure�
The internal temperature sensor has failed�
Contact AutomationDirect�
300-307
Thyristor Firing Trip
One or more of the internal control thyristors (SCRs) have failed to turn on properly (In-Line
“Firing Mode”)
The SR55 has detected that the SCRs are not operating as expected�
Check all incoming and outgoing connections�
350-357
Thyristor Firing Trip
One or more of the internal control thyristors (SCRs) have failed to turn on properly (Delta “Firing
Mode”)�
The SR55 has detected that the SCRs are not operating as expected�
Check all incoming and outgoing connections�
401
Motor Side Phase
Loss
One or all of the phases are missing on the motor side during the instant of start up
T1, T2, or T3 are missing or at a very low level�
Check that the motor is connected to T1, T2 and T3�
Ensure any disconnecting device between the SR55 and the motor is closed at the instant of
start up�
402-403
Motor Side Phase
Loss
One or all of the phases are missing on the motor side during the instant of start up when the
motor is being controlled�
T1, T2 or T3 are missing or at a very low level�
Check all incoming and outgoing connections�
601
Control Voltage Too
Low
The internal control supply of the SR55 level has fallen to a low level�
Can be caused by a weak 24VDC/115VAC/230VAC control supply
Ensure 24VDC/115VAC/230VAC supply meets the requirements specified in “Electrical
Installation” Chapter 2 or the Quick Start Guide�
701-710
Sensing Fault Trip
One or more of the internal control thyristors (SCRs) have failed to turn on properly
The SR55 has detected that the SCRs are not operating as expected�
Check connections all incoming and outgoing connections�
801-802
Fan Problem
One or more of the internal cooling fans has failed�
To ensure the heatsink is cooled sufficiently, the SR55 will trip if the fans fail to operate�
Check SR55 fans for signs of damage or contamination�
1001
Short Circuit
Thyristor
One or more of the internal control thyristors (SCRs) have failed short circuit�
The SR55 has detected that the SCRs are not operating as expected�
Check all incoming and outgoing connections�
1101
Low Current Trip
The motor current has been lower than the “Low Trip Level” for the “Low Trip Time” (under
“Motor Protection”)�
This trip is not active during soft start and soft stop and is “off” by default�
If the Low Current Trip is not required, turn “off” in “Trip Settings�

Table of Contents

Related product manuals