Page 3–78 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
parameTer deTails (ConTinued)
“deviCe” menu of parameTers
P25.0 – Update Firmware Type:
Description:
Read/Write
Used to upgrade to the latest version of firmware using a USB
ash drive
.
Range: Modbus Decimal Value: Default:
n/a n/a n/a
Modbus Address: Modbus Format:
n/a n/a
Touchscreen Menu Path:
Home → Device → Update Firmware
P25.1 – Date Type:
Description:
Read/Write
Enter current date.
• Date format can be set to either dd/mm/yyyy or mm/dd/yyyy; refer to “Date format” parameter.
Range: Modbus Decimal Value: Default:
• dd/mm/yyyy
• mm/dd/yyyy
n/a n/a
Modbus Address: Modbus Format:
See “Time” parameter for date address. n/a
Touchscreen Menu Path:
Home → Device → Date
P25.2 – Time Type:
Description:
Read/Write
Allows the time to be changed to ‘local’ time.
Range: Modbus Decimal Value: Default:
hh:mm:ss Time(ms) since midnight
(bytes5,4,3,2) and Days since
01/01/1984 (bytes1,0)
GMT
Modbus Address: Modbus Format:
14720 ( 3980 hex ) 6 Bytes
Touchscreen Menu Path:
Home → Device → Time
Time derivaTion example
Time is derived from the number of milliseconds since midnight.
Date can be derived from the number of days since midnight 1st Jan 1984.
If Modbus addresses 14720 thru 14724 (6 bytes) and the time is 09:50 and the date is 9th March
2015, then the SR55 will return: 021C49782C7E.
Where: 021C4978 = # milliseconds since midnight, and 2C7E = # days since 01/01/84.
Since there are 60 seconds in a minute, 3600 seconds in an hour, and 86400 seconds in a day,
the time can be derived as follows:
•
021C4978h = 35407992d (ms) = 35407 (s)
•
Hour = 35407 mod 86400/3600 = 09
•
Min = 35407 mod 3600/60 = 50
•
Sec = 35407 mod 60 = 07
So the time is 09:50:07.
For the date the SR55 will only return the number of days since 01/01/84.
So: 2C7Eh = 11390d.