Chapter 3: Configuration and Parameters
Page 3–79Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
parameTer deTails – “deviCe” menu of parameTers (ConTinued)
P25.3 – Language Hold. Reg. Type:
Description:
Read/Write
Selects the display language for the touchscreen.
Enter the required language from the displayed list.
Range: Modbus Decimal Value: Default (decimal):
ENG
DEU
FRA
ITA
CHN
TUR
POR
JPN
SRB
RUS
VIE
KOR
1
2
3
4
5
6
7
8
9
10
11
12
English (1)
Modbus Address: Modbus Format:
13376 ( 3440 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Device → Language
P25.4 – Passcode Type:
Description:
Read/Write
Stops unauthorized access to read/write parameters.
The “Screen lock” must be turned on for the passcode be active.
With passcode protection on, the SR55 can still be started and stopped. The Log and Monitor
screens can also still be accessed.
Range: Modbus Decimal Value: Default:
0 – 9 per Byte (ASCII character) 48–57 (48 = “0” ... 57 = “9”) n/a
Modbus Address: Modbus Format:
12864 ( 3240 hex ) – Byte 3 (MSB)
12865 ( 3241 hex ) – Byte 2
12866 ( 3242 hex ) – Byte 1
12867 ( 3243 hex ) – Byte 0
16-bit unsigned
16-bit unsigned
16-bit unsigned
16-bit unsigned
Touchscreen Menu Path:
Home → Device → Passcode
warning: if a passcode is seT in The sr55 and losT/forgoTTen, you musT conTacT Technical
supporT for assisTance (800) 633-0405. The procedure will require The uniT be facTory reseT by an
auThorized represenTaTive.
P25.5 – Backlight Timeout Type:
Description:
Read/Write
Time for backlight on display.
After the period set, the back light on the screen will turn off.
To reactivate, touch screen anywhere.
To disable, set to 0.
Range: Modbus Decimal Value: Default:
0s – 3600s linear scale ( 1 = 1 s ) 60s
Modbus Address: Modbus Format:
14208 ( 3780 hex ) 16-bit unsigned
Touchscreen Menu Path:
Home → Device → Backlight Timeout

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals