Page 3–86 Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
Chapter 3: Configuration and Parameters
fAIl sAfe codes
main board Trip (2402 – 2436)
A trip number in the range of 2402 to 2436 indicates that a process on the main board has
been affected in some way and is unable to recover automatically.
The trip is turned ON and OFF via the “Main Board Trip” (Advanced / Trips)�
The default for this trip is ON�
The trip MUST be reset using the either the digital input, touchscreen, or bus command
depending on the Control Method set�
As this is a special case, it is NOT possible to reset this trip by cycling the control supply
Fail Safe Codes Associated with the Main Board
Code # Description
2402 Initialization process has been unsuccessful�
2404 Initialization of the Parameters has been unsuccessful�
2406 Initialization of the Overload has been unsuccessful�
2408 Initialization of the Parameter Read has been unsuccessful�
2410 Initialization of the Overload Read has been unsuccessful�
2412 Initialization of the Current measurement has been unsuccessful�
2420 A main process on the Main Board has been affected and is unable to recover automatically
2422 A main process on the Main Board has been affected and is unable to recover automatically
2424 A main process on the Main Board has been affected and is unable to recover automatically
2426
Communication between the Main Board and Touchscreen Board has been affected and is unable to recover
automatically
2428 The modbus communication has been affected and is unable to recover automatically
2430 The parameter save has been unsuccessful�
2432 The logging function has been unsuccessful�
2434 A main process on the Main Board has been affected and is unable to recover automatically
2436 The Anybus communication has been affected and is unable to recover automatically
TouChsCreen Trip (2501 – 2581)
A trip number in the range of 2501 to 2581 indicates that a process on the touchscreen board
has been affected in some way and is unable to recover automatically.
The trip is turned ON and OFF via the “Touchscreen Trip” (Advanced / Trips)�
The default for this trip is OFF
With the trip OFF the touchscreen display may display the ‘start up’ screen momentarily as it
recovers automatically
When the trip is turned ON it is reset using the either the digital input or touchscreen or bus
command, depending on the Control Method set�
It is possible to reset this trip by cycling the control supply
Fail Safe Codes Associated with the Touchscreen Board
Local Touchscreen Code Remote Touchscreen Code Description
2501 – 2529 2551 – 2579
A main process on the Touchscreen Board has been
affected�
2530 2580
Communication between the Main board and Touchscreen
Board has been affected�
2531 2581 The touchscreen has become unresponsive�
When a remote touchscreen is used the same trips can be generated. However, to discriminate
between the remote and local (built in) 50 is added to each code.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automation Direct Stellar SR55 Series and is the answer not in the manual?

Automation Direct Stellar SR55 Series Specifications

General IconGeneral
BrandAutomation Direct
ModelStellar SR55 Series
CategoryController
LanguageEnglish

Related product manuals