6.Parametersettingandfunctions
33
©CopyrightReservedAutonicsCo.,Ltd.
6.2.3 Startlimit[
S-LM
]andstartlimittime[
S-LT
]
When power is ON, changing to RUN status from STOP status, or alarm reset, set limit output
value and time to prevent the inrush current or error current.
A: Soft start [
ST-T
] function ends
B: Slow up [
UP-T
] function ends
C: Slow down [
DN-T
] function ends
Regardless of control method setting (phase control or cycle control), it operates as phase control.
• Start limit [
S-LM
] set range: 0 to 110 of output (unit: %)
• Start limit time [
S-LT
] set range: 0 to 100 sec.(unit: sec.)
6.2.4 Outputslopesetting[
SLOP
]
This function is to set output changed ratio by control input from 0.00 to 1.00 range.
Output value when setting slope is input(%) X slope value.
Output(%)
Start
limit
SOFT START set time
Start limit set time
Time
SLOW UP set time
SLOW DOWN set time
Output(%)
Control input signal(%)
Output slope
value(%)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics Digipower 2000 and is the answer not in the manual?

Autonics Digipower 2000 Specifications

General IconGeneral
BrandAutonics
ModelDigipower 2000
CategoryController
LanguageEnglish

Related product manuals