9.ModbusMappingTable
52
©CopyrightReservedAutonicsCo.,Ltd.
9.5.2 Holdingresisters
Address Item Factor
400001(0000) Reference value *0.1(1 to 1000)
400002(0001) Start time 0 to 99
400003(0002) Start limit *0.1(1 to 1000)
400004(0003) Soft start time 0 to 99
400005(0004) Output high-limit *0.1(1 to 1000)
400006(0005) Output low-limit *0.1(1 to 1000)
400007(0006) Remote SP1 *0.1(1 to 1000)
400008(0007) Remote SP2 *0.1(1 to 1000)
400009(0008) Remote SP3 *0.1(1 to 1000)
400010(0009) Remote SP4 *0.1(1 to 1000)
400011(000A) Remote SP5 *0.1(1 to 1000)
400012(000B) Remote SP6 *0.1(1 to 1000)
400013(000C) Slow up time 0 to 99
400014(000D) Slow Stop time 0 to 99
400015(000E) Current limit *0.1(1 to 2000)
400016(000F) Over current value *0.1(1 to 1100)
400017(0010) Over current time 0 to 99
400018(0011) Over voltage value *0.1(1 to 1100)
400019(0012) Over voltage time 0 to 99
400020(0013) Load detector alarm value *0.1(1 to 2000)
400021(0014) Display selected contents 0 to 3
400022(0015) Bar graph's content 0 to 3
400023(0016) Control integer KP value 1 to 9999
400024(0017) Control integer KI value *0.1(1 to 999.9)
400025(0018) Control method 0 to 6
400026(0019) Digital input 1 0 to 4
400027(001A) Digital input 2 0 to 4
400028(001B) Digital input 3 0 to 4
400029(001C) Auto ref input selector 0 to 3
400030(001D) Load resistance display method 0 to 1