In the Event of a Fire Alarm
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 28
Step Actions to be taken Display Indication Audible Indication
3
Use the arrow down
(/arrow up) button and
scroll to observe the
detection zones and
point(s) in alarm state.
Comments: In this example, a total of 2 detection zones are in alarm state. If you want to
view detailed zonal/point information for each zone before investigating the
scene(s), go to step 5. If not, investigate the scene(s), then go directly to step
7.
4
Investigate the scene(s)
and carry out the
necessary actions.
5
To select a point, scroll
with the arrow up/down
buttons.
6
To view detailed point
information, press
then scroll downwards
to see all information.
Comments: If you want to view detailed information for another point;
move back using the Cancel button
, then select another point in
step 5 and repeat step 6. If not, go directly to step 7.
7
To silence all alarms,
press the red Silence
button.
All Fire Alarm Devices
(FAD) are deactivated.
The Alarm indicator goes
steady.
Comments: The red Alarm indicator goes steady.
To manually resound the alarm zones at this stage, press and hold down the
Silence button at least 10 seconds (see countdown of seconds on display).
Configurable: A timer begins to count down. The alarm zones are
automatically resounded to their alarm states on timeout of the silence
resound timer.
When the fire is extinguished and all necessary repair work is implemented
(smoke is exhausted, new glass replaced in the manual call points, etc.), the
system should be returned to normal operation mode (step 8).
8
Press the green Reset
button.
All audible indicators on
all panels in the system
are turned off.