■ Heat/Cool control dead band setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [C28: Heat/Cool control
dead band].
(4) Press the [<], [], or []key to change the set value
in [C28].
Setting range: -100.0 to +100.0 (%)
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.