5-29
Chapter 5. SETTINGS BEFORE STARTING OPERATION
■ Output scaling low limit/high limit setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [C44: Output 1 scaling low
limit] or [C45: Output 1 scaling high limit].
(4) Press the [<], [], or []key to change the set value in [C44] and [C45].
Setting range: -1999 to +9999
The decimal point position and unit are changed corresponding to the output
type.
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
The following figures show the relationship between the output and the numeric
value of the output type by output scaling low limit/high limit setup:
Handling Precautions
• The displays of the output 2 scaling low limit and high limit are [C49]
and [C50].
• When the control output 1 of the model is set at “current”, [C44] and
[C45] are displayed.
When the control output 2 of the model is set at “current”, [C40] and
[C50] are displayed.