5-38
Chapter 5. SETTINGS BEFORE STARTING OPERATION
■ User level setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting [C79: User level].
(4) Press the [<], [], or []key to set the value you have
selected from the following in [C79].
0: Simple configuration
1: Standard configuration
2: High function configuration
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
Handling Precautions
When [User level] is set at [Standard configuration] or [High function
configuration], the description of this manual is insufficient. In this
case, refer to Single Loop Controller SDC15 User's Manual
"Installation & Configurations" (CP-SP-1148E).