INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-409A 2 - 3
Configuring Dipswitches
Configure the termination module for the types of inputs and
outputs desired using dipswitches S1 through S5. Tables 2-1
and 2-2 show the possible dipswitch settings.
Cable Connections
The NICS01 Controller/Station Termination Module termi-
nates analog and digital I/O signals, and interfaces them
directly to a master/slave module. Figures 2-2, 2-3, and 2-4
show the cables to use and their connections for several differ-
ent applications of the ICS module. Table 2-3 lists each cable
and its application. See Figure 2-1 for the location of cable
connectors P1, J1 and J2.
Table 2-1. Switch S1, S2, S3 and S4 Settings
Analog Input
Signal Type
Switch Position
12345678
System powered (4-20 mA) 1 1 1 1 1 1 0 0
Externally powered (4-20 mA) 0 0 0 0 1 1 1 1
Single ended voltage (1-5 VDC) 0 0 0 1 0 1 1 1
Differential voltage (1-5 VDC) 0 0 0 0 0 0 1 1
NOTE:
0 represents the OPEN or OFF side of the switch. 1 represents the CLOSED or ON side of
the switch.
Table 2-2. Switch S5 Settings
Analog Output
Signal Type
Switch Position
1,2
1234
Both outputs are 1-5 VDC 1111
Analog Output 1 is 1-5 VDC,
Analog Output 2 is 4-20 mA
1100
Analog Output 1 is 4-20 mA,
Analog Output 2 is 1-5 VDC
0011
Both outputs are 4-20 mA 0000
NOTES:
1. 0 represents the OPEN or OFF side of the switch. 1 represents the CLOSED
or ON side of the switch.
2. Switch Positions 1 and 2 represent Analog Output 1 and Switch positions 3
and 4 represent Analog Output 2.
Figure 2-2. NICS01 Cable Connections to One Station
IMCOM03/04
IMCIS02
IMQRC01
IMQRS02
NDIS01
NDCS03
IISAC01
NO ANALOG OUTPUT BYPASS CAPABILITY
T00498A
P3 P1 P1
J1
J2
NKTM01
NKTU02/12
NKTD02/12
NICS01