NDCS03 DIGITAL CONTROL STATION CONFIGURATION
INTRODUCTION
I-E96-409A F - 3
Table F-3. Switch S1 Settings
Station
Address
Switch Position
123
0 000
1 001
2 010
3 011
4 100
5 101
6 110
7 111
NOTE:
0 represents the CLOSED or ON side of the
switch. 1 represents the OPEN or OFF side of the switch.
Table F-4. Jumpers J1 through J5 Settings
Jumper
Jumper
Position
Function
JP1 1-2
2-3
Enable auto bypass.
Disable auto bypass.
JP2 1-2
2-3
Enable reverse acting output when in bypass.
Disable reverse acting output when in bypass.
JP3 1-2
2-3
No external analog input displayed on OUT bar
graph when in normal mode of operation.
External analog input displayed on OUT bar
graph when in normal mode of operation.
JP4 1-2
2-3
External analog input displayed on OUT bar
graph when in bypass mode of operation.
External analog input displayed on VAR bar
graph when in bypass mode of operation.
JP5 1-2
2-3
Select bright intensity.
Select dim intensity.