2.3.4 Wire sizes
Input and output wire size is based on the use of copper conductor wire rated at 167°F (75°C).
The following tables describe the wire size to be used for power connections and the ratings of the
protection devices.
Catalog Number
Incoming Power
Input
Nominal Continuous
D-T
pe
Fuse
re
auge
Input
Voltage
Output
Amps
(RMS)
nput
Breaker
(A)
Time
Delay
(A)
AWG mm
2
MD1A02xx-xxxx 115V (1φ) 2.5A 6 6 14 2.5
MD2A02xx-xxxx 230V (1φ) 2.5A 6 6 14 2.5
MD1A05xx-xxxx 115V (1φ) 5A 10 10 14 2.5
MD2A05xx-xxxx 230V (1φ) 5A 10 10 14 2.5
MD1A07xx-xxxx 115V (1φ) 7.5A 16 16 14 2.5
MD2A07xx-xxxx 230V (1φ) 7.5A 16 16 14 2.5
MD1A10xx-xxxx 115V (1φ) 10A 20 20 14 2.5
MD2A10xx-xxxx 230V (3φ) 10A 20 20 14 2.5
MD1A15xx-xxxx 115V (1φ) 15A 32 32 12 2.5
MD2A15xx-xxxx 230V (3φ) 15A 32 32 12 2.5
Note: All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may
be used per NEC and local codes. Recommended fuses/breakers are based on 77°F (25°C)
ambient, maximum continuous control output current and no harmonic current.