18 english
NOTICE!
Interference in function
Teach-in while the system is running may result in 
malfunctions.
 ► Stop the system before performing teach-in.
LED display Displayed values (example)
LED1 LED2 At 0 to 10 V At 4 to 20 mA
Initial situation:
–  Transducer with magnet within measuring range
5.39 V 9.15 mA
1. Activate buttons
 ► Hold down any button for at least 3s.
> 3 s
2
1
5.39 V 9.15 mA
 ► Release button.
< 1 s
 ► Within 1s, hold down 
 and 
 simultaneously for at 
least 3s.
> 3 s
1
2
 ⇒ Output indicates error value.
10.50 V 3.60 mA
 ⇒ Buttons are activated.
If an error or an interruption occurs while 
activating the buttons, allow a wait time of 12s 
before retrying.
2. Select teach-in
 ► Hold down 
 for at least 2s.
> 2s
 ⇒ Indication for "Teach-in" is displayed.
4.00V 12.00 mA
 ► Release 
.
 ⇒ Current position value is displayed.
5.39 V 9.15 mA
3. Set null point
 ► Bring magnet to the new null point.
 
1.04 V 4.82 mA
 ► Hold down 
 for at least 2s.
> 2s  
1
0.00 V 4.00 mA
 ⇒ The new null point is set.
0.00 V 4.00 mA
4. Set end point
 ► Bring magnet to the new end point.
9.89 V 19.13 mA
 ► Hold down 
 for at least 2s.
> 2s  
2
10.00 V 20.00 mA
 ⇒ The new end point is set.
10.00 V 20.00 mA
5. Exit teach-in and deactivate buttons
 ► Hold down 
 and 
 simultaneously for at least 6s. > 6s
 
1
2
10.50 V 3.60 mA
 ⇒ Output indicates error value.
 ► Briefly press 
 or 
 (<1s).
< 1s  
2
1
 ⇒ Buttons are deactivated.
 
 ⇒ Current position value is displayed.
10.00 V 20.00 mA
LED legend: LED not on LED flashing green
LED green
LED 1 and LED 2 flashing green-green in alternationLED red
7 
Calibration using teach-in
1
BTL7-A/C/E/G_ _ _-M_ _ _ _-A/B/Y/Z(8)-S32/S115/S135/S140/KA_ _/FA_ _
Micropulse Transducer - Rod Style