3. Press Select to confirm the new distance value. The new distance value flashes rapidly, the new setting is accepted,
and the sensor returns to Run mode.
3.2.2 Manual Adjustments in One-Point TEACH Mode
Adjust the 5 V (12 mA) Midpoint
1.
From Run mode, press
to view and adjust the distance setting associated with the 5 V (12 mA) midpoint (the mid
point of the analog span). displays briefly, then the value slowly flashes indicating it can be changed.
Note: If no changes are made within 8 seconds, the current distance value flashes quickly and the
sensor returns to Run mode.
2. Press
to move the midpoint up or to move the midpoint down.
Note: If no additional changes are made within 4 seconds, the current distance value flashes
quickly and the sensor returns to Run mode.
3. Press Select to confirm the new midpoint. The new midpoint value flashes rapidly, the new setting is accepted, and
the sensor returns to Run mode.
Adjust the Analog Window Size
1. Press
to view and adjust the SPAN (the analog window size). flashes briefly, then the value flashes.
2. Press to increase the size of the analog window or to decrease the size of the analog window.
3. Press Select to confirm the window size. The new window size flashes rapidly, the new setting is accepted, and the
sensor returns to Run mode.
3.3 Remote Input
Use the remote input to program the sensor remotely. The remote input provides limited programming options and is Active
low. For Active low, connect the gray input wire to ground (0 V dc), with a remote switch connected between the wire and
ground. Pulse the remote input according to the diagram and the instructions provided in this manual.
The length of the individual programming pulses is equal to the value T: 0.04 seconds ≤ T ≤ 0.8 seconds.
Exit remote programming modes by setting the remote input
low for longer than 2 seconds.
Figure 20. Remote Input Map
2x
1x
Teach 10 V (20 mA)
Save 10 V (20 mA)
1x
2x
Teach Selection
Enters selected Teach (same function as pressing Teach Button for > 2 sec)
1x
Teach 0 V (4 mA)
0.04 seconds < T < 0.8 seconds
Timing between Pulse groups > 1 second
Pulse Timing (T)
Input = Set
Gray wire is remote teach input
2x
1x
Two-point Teach
One-point Teach
4x
2x
1x
Button Unlock (uloc)
Button Lock (loc)
Button Lock
8x
Reset to Factory Defaults (maintain remote input = SET)
Remote
Input
2x
Save 0 V (4 mA)
2x
1x
Teach 10 V (20 mA)
Save 10 V (20 mA)
3x
Operator Lock (OLoc)
Q4X Stainless Steel Analog Laser Sensor
www.bannerengineering.com - Tel: + 1 888 373 6767 17

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Banner Q4X Series and is the answer not in the manual?

Banner Q4X Series Specifications

General IconGeneral
BrandBanner
ModelQ4X Series
CategoryAccessories
LanguageEnglish

Related product manuals