SC22-3 Safety Controller
Instruction Manual
Appendix B
Add Other Safety Input Devices
The steps required to add other safety input devices are
similar to those described above. Add a Gate Switch to the
configuration:
• Click on the Add Safety Input button on the tool bar.
• Double-click on the Gate Switch icon.
• Create a Gate Switch configuration with the properties listed
below.
Name: GS01
Circuit: Single-channel, 2 terminals
Reset: Automatic
Terminals: S5 and S6
Map to: SO1 and SO2
(Click on a checkbox to select or deselect it.)
Your Gate Switch properties menu should match the one shown
above.
• Click OK.
Add a Two-Hand Control Input Device
• Click on Add Safety Input.
• Double-click on the Two-Hand Control icon.
• Create a Two-Hand Control configuration with the properties
listed below.
Name: THC01
Circuit: 2X complementary, PNP switch
Terminals: S7, S8, S9 and S10
Map to: SO3
• Click OK.
NOTE: The reset logic is set to Automatic for Two-Hand Control
devices. There are no other reset options.
Add an Optical Sensor Input Device
• Click on Add Safety Input.
• Double-click on the Optical Sensor icon.
• Create an Optical Sensor configuration with the properties
listed below.
Name: OS01
Circuit: Dual Channel, PNP switch
Reset: Automatic
Terminals: S11 and S12 (Use the drop-down terminal number
fields to change the terminal assignment, if
needed.)
Map to: SO1 and SO2
• Click OK.