106 P/N 133487
Banner Engineering Corp. • Minneapolis, U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
SC22-3 Safety Controller
Instruction Manual
Appendix B
Add a Mute Sensor Pair
• Click on Add Safety Input.
• Double-click the Mute Sensor icon.
• Create a Mute Sensor configuration with the properties listed
below.
Name: M1+M2
Circuit: Dual-Channel, 4 Terminal
Terminals: S13, S14, S15, and S16
(Use the drop-down terminal number fields to
change the terminal assignment, if needed.)
Map to: OS01
Time limit: 1 minute, 0 second
• Click OK.
NOTE: Mute sensors are mapped to the safety input devices that
they mute and not to the safety outputs.
Add an External Device Monitoring Input
• Click on Add Safety Input.
• Double-click the External Device Monitoring icon.
• Create an External Device Monitoring configuration with the
properties listed below.
Name: EDM01
Circuit: Single Channel, 1 terminal
Reset: Automatic
Terminals: S17 (Use the drop-down terminal number field to
change the terminal assignment, if needed.)
Map to: SO1
• Click OK.
Add More External Device Monitoring Inputs
Add two more External Device Monitoring inputs, one for each
safety output.
• Name them EDM02 and EDM03.
• Use Single-Channel, 1-terminal circuit types for each.
• Assign terminal S18 to EDM02 and terminal S19 to EDM03.
• Map EDM02 to SO2 and EDM03 to SO3.