Procedure of the commissioning
Instruction handbook b maXX (BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08 Baumüller Nürnberg GmbH
46
of 82
8.2
4 Choose submenu „Service“
This window shows the position/slot of the recognized Analog IO module.
If the Analog IO module is available in position/slot D, then the following is displayed:
„Slot D Analog IO 16 Bit Version X“.
„X“ shows the version of the module.
Always available with the ES controller is the module AIO-01 (position E), a further
AIO-02/03/04 can be used additionally.
5 Decide on the basis of the display:
Figure 11: ProDrive Service
m If the Analog IO module has been correctly recognized, the commissioning can be
continued, refer to Instruction Handbook b
maXX 4000, 5.12008 or Parameter Man-
ual b maXX 4000, 5.03039.
m If the Analog IO module has not been correctly recognized, turn off the device,
check the mounting and the installation. After removing all errors, switch on the de
-
vice again.
m If the Analog IO module has not been correctly recognized again, it is defect or the
controller/controller slot (of standard controller) is defect. Contact Baumüller Nürn
-
berg GmbH for replacement.
Analog I/O 16 Bit
BM4-F-AIO-02
Analog I/O 8/10 Bit
BM4-F-AIO-01
Version B
Version B