EasyManuals Logo

Bender ISOMETER IRDH375 User Manual

Bender ISOMETER IRDH375
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
Connection
41
IRDH375_D00124_05_M_XXEN/01.2020
The maximum DC voltage is the voltage permitted to occur in the AC part of
an IT system to PE when the IRDH375 is coupled with AGH204S-4 in this part
of the system. This voltage is dependent on the level of the nominal voltage,
the type of rectification 6 pulse, 12 pulse,…), the type of converter intermedi-
ate circuit (current… or voltage…), and the converter technology. In case of
converters, the maximum DC voltage in the intermediate circuit usually corre-
sponds to the phase-to-phase voltage of the supplying AC system multiplied
by 1.414.
In case of current-controlled intermediate circuits of frequency converters,
higher DC voltages are to be expected.
The given voltage values for AC/DC systems take into account values found by
previous experience (factor 1.414 between DC voltage and AC voltage).
The maximum DC voltage in case of insulation faults in the DC part of the IT
system, for example converter intermediate circuit, is DC 1840 V. From this,
the maximum nominal AC voltage is calculated:
U
max
= DC 1,840 V/1.414 = AC 1,300 V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER IRDH375 and is the answer not in the manual?

Bender ISOMETER IRDH375 Specifications

General IconGeneral
BrandBender
ModelISOMETER IRDH375
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals