Function
24
isoRW425_D00052_03_M_XXEN / 02.2017
With "Adr = 0", the menu entries baud rate and parity are not
shown in the menu and the IsoData protocol is activated.
With a valid bus address (i.e. not equal to 0), the menu item
"baud rate" is displayed in the menu. The parameter value
"---" for the baud rate indicates the activated BMS protocol. In
this event, the baud rate for the BMS protocol is set to 9600
baud. If the baud rate is set unequal to "---", the modbus
protocol with configurable baud rate is activated.