EasyManuals Logo

Bender ISOMETER isoRW425 User Manual

Bender ISOMETER isoRW425
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Installation, connection and commissioning
27
isoRW425_D00052_03_M_XXEN / 02.2017
4.2 Connection
Connect the terminals A1 and A2 to the supply voltage according to
IEC 60364-4-43, i.e. the connections are to be protected against short-circuit
by means of a protective device (a 6 A fuse is recommended).
Devices for protection against short-circuit in conformity with IEC 60364-4-43
for the coupling of terminals L1/L2 to the IT system to be monitored can be
omitted if the wiring is carried out in such a manner as to reduce the risk of a
short-circuit to a minimum.
Only one ISOMETER® may be controlled via a test/reset button. It is not al-
lowed to use a parallel connection of several test or reset inputs for combined
testing of ISOMETER®s.
For UL application:
Only use 60/70°C copper lines!
For UL and CSA applications, it is mandatory to use 5 A fuses for the protection
of the supply voltage.

Table of Contents

Other manuals for Bender ISOMETER isoRW425

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER isoRW425 and is the answer not in the manual?

Bender ISOMETER isoRW425 Specifications

General IconGeneral
BrandBender
ModelISOMETER isoRW425
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals