EasyManua.ls Logo

Bender ISOMETER isoRW425 - Technical Data; Tabular Presentation

Bender ISOMETER isoRW425
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
isoRW425_D00052_03_M_XXEN / 02.2017
10. Technical data
10.1 Tabular presentation
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Definitions:
Measuring circuit (IC1) ...........................................................................................................................L1/+, L2/-
Supply circuit (IC2) ....................................................................................................................................... A1, A2
Output circuit (IC3)................................................................................................................................... 11, 14, 24
Control circuit (IC4) ...........................................................................................................................E, KE, T/R, A, B
Rated voltage......................................................................................................................................................... 400 V
Overvoltage category.....................................................................................................................................................III
Rated impulse voltage:
IC1 / ( IC2-4 ).......................................................................................................................................................6 kV
IC2 / ( IC3-4 )...................................................................................................................................................... 4 kV
IC 3 / ( IC4 )......................................................................................................................................................... 4 kV
Rated insulated voltage:
IC1 / ( IC2-4 ).................................................................................................................................................... 400 V
IC2 / ( IC3-4 )................................................................................................................................................... 250 V
IC 3 / ( IC4 )...................................................................................................................................................... 250 V
Polution degree.............................................................................................................................................................. 3
Protective separation (reinforced insulation) between:
IC1 / ( IC2-4 )........................................................................................................... Overvoltage category III, 600 V
IC2 / ( IC3-4 )........................................................................................................... Overvoltage category III, 300 V
IC 3 / ( IC4 ).............................................................................................................. Overvoltage category III, 300 V
Voltage test (routine test) according to IEC 61010-1:
IC2 / ( IC3-4 )............................................................................................................................................. AC 2,2 kV
IC 3 / ( IC4 )................................................................................................................................................ AC 2,2 kV
Supply voltage
Supply voltage U
s
...................................................................................................... AC 100…240 V/DC 24…240 V
Tolerance of U
s
........................................................................................................................................ -30…+15 %

Table of Contents