EasyManua.ls Logo

Bender ISOMETER isoRW425 - Page 41

Bender ISOMETER isoRW425
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Device operation
41
isoRW425_D00052_03_M_XXEN / 02.2017
: The measuring value can be displayed in the history memory.
± R %
Fault location in %
-100% …+100% Indication only from U
n
20 V
DC
R
L1F
= (200% * R
F
) / (100% + x%)
R
L2F
= (200% * R
F
) / (100% - x%)
-
U R = k
Insulation resistance R
UGF
1 k … 4 M Resolution 1 k / 10 k
Indication only from U
n
20 V
DC
R
UGF
is an approximate value for asymmetrical insula-
tion faults and can be used as a trend indicator with
short measuring times. Not available in Z mode.