2.3.1 Standard Duty (350% for 30 sec) Ratings
z NOTE: Do not exceed Class 10 overload setting.
14
2 - TECHNICAL SPECIFICATIONS
Standard Duty (350% current for 30 seconds, 115% Continuous)
MODEL NUMBER
NOMINAL
AMPS
HORSEPOWER RATING
200-208V 230-240V 380-400V 440-480V 575-600V
RB2-1-S-027A-11C 27 7.5 10 15 20 25
RB2-1-S-040A-11C 40 10 15 25 30 40
RB2-1-S-052A-12C 52 15 20 30 40 50
RB2-1-S-065A-12C 65 20 25 40 50 60
RB2-1-S-077A-13C 77 25 30 40 60 75
RB2-1-S-096A-13C 96 30 40 50 75 100
RB2-1-S-125A-14C 125 40 50 75 100 125
RB2-1-S-156A-14C 156 50 60 75 125 150
RB2-1-S-180A-14C 180 60 75 100 150 200
RB2-1-S-180A-15C 180 60 75 100 150 200
RB2-1-S-240A-15C 240 75 100 150 200 250
RB2-1-S-302A-15C 302 100 125 150 250 300
RB2-1-S-361A-16C 361 125 150 200 300 400
RB2-1-S-414A-17C 414 150 150 250 350 400
RB2-1-S-477A-17C 477 150 200 300 400 500
RB2-1-S-515A-17C 515 200 200 300 450 500
RB2-1-S-590A-18C 590 200 250 350 500 600
RB2-1-S-720A-19C 720 250 300 400 600 700
RB2-1-S-838A-20C 838 300 350 500 700 800
Table 4: Standard Duty Horsepower Ratings