2.3.8 RB2 Starter Control Power Requirements
2.3.9 RC2 Starter Control Power Requirements
21
2 - TECHNICAL SPECIFICATIONS
Model Number
Power
Required
(VA)
Recommended
Min. TX size
Model Number
Power
Required
(VA)
Recommended
Min. TX size
RB2-1-S-027A-11C 74 75 RB2-1-S-240A-15C 243 250
RB2-1-S-040A-11C 74 75 RB2-1-S-302A-15C 243 250
RB2-1-S-052A-12C 111 125 RB2-1-S-361A-16C 243 250
RB2-1-S-065A-12C 111 125 RB2-1-S-414A-17C 441 450
RB2-1-S-077A-13C 111 125 RB2-1-S-477A-17C 441 450
RB2-1-S-096A-13C 111 125 RB2-1-S-515A-17C 441 450
RB2-1-S-125A-14C 131 150 RB2-1-S-590A-18C 441 450
RB2-1-S-156A-14C 243 250 RB2-1-S-720A-19C 441 450
RB2-1-S-180A-14C 243 250 RB2-1-S-838A-20C 243 250
Table 8: RB2 Starter CPT VA Requirements
Model Number
Power
Required
(VA)
Recommended
Min. TX size
Model Number
Power
Required
(VA)
Recommended
Min. TX size
RC2-1-S-027A-31C 45 75 RC2-1-S-240A-35C 123 150
RC2-1-S-040A-31C 45 75 RC2-1-S-302A-35C 123 150
RC2-1-S-052A-31C 45 75 RC2-1-S-361A-35C 201 250
RC2-1-S-065A-32C 45 75 RC2-1-S-414A-35C 150 200
RC2-1-S-077A-32C 45 75 RC2-1-S-477A-35C 225 350
RC2-1-S-096A-33C 45 75 RC2-1-S-590A-35C 225 350
RC2-1-S-124A-33C 45 75 RC2-1-S-720A-36C 225 350
RC2-1-S-125A-34C 123 150 RC2-1-S-840A-19C 225 350
RC2-1-S-156A-34C 123 150 RC2-1-S-960A-20C 225 350
RC2-1-S-180A-34C 123 150 RC2-1-S-1200A-37C 285 350
Table 9: RC2 Starter CPT VA Requirements