4.13.2 Meter Pages
Although any meter may be viewed by changing the two Meter parameters (FUN 01 & FUN 02), there are 13 “Meter Pages” that are
easily accessed to view all of the meter information. These meter pages are scrolled through by pressing the [UP] or [DOWN] down
arrows from the operate screen.
z NOTE: Run Hours 00:00 – 23:59
Run Days 0 – 2730 days or 7.5 years
kWatt Hours 0 – 999
MWatt Hours 0 – 9999
Starts 0 – 65535
4.13.3 Fault Log Screen
More information regarding each fault is available through the remote MX
2
LCD display than is available through the standard MX
2
LED display.
FL _: = Fault Log Number. FL1 is the most recent fault and FL9 is the oldest fault.
Fault _ _ = Fault Code
NNN… = Fault Name, or the condition when the fault occurred.
56
4 - KEYPAD OPERATION
Current I2 = 0.0A
I1 = 0.0 I3 = 0.0A
RS Gnd Cur= 0%
Voltage V2= 0V
V1= 0 V3= 0V
Lst STt Tim= xx.xs
Pk ST Cur = xx.xA
MWatt Hour = 0
kWatt Hour = 0
Frequency = 60.0H
Phase = AbC
Watts = 0
VA = 0
Run Days = xxxx
Run Hours = xx:xx
Motor PF = 0.00
vars = 0
Analog In = 0.0%
Analog Out = 0.0%
TruTorque = 0%
Power = 0%
Starts = xxxxx
Overload = 0%
Curr Inbal = 0.0%
FL#: Fault##
NNNNNNNNNNNNN