126
PID High Alm AFN 37
PID Low Alm AFN 38
PID Sleep AFN 39
AFN: PID High Alm
37 0.00%
AFN: PID Low Alm
38 0.00%
AFN: PID Sleep
39 Disabled
7 - PARAMETER DESCRIPTION
LCD Display
Range 0.00 to 100.00% (Default 0.0%)
Description PID high alarm. When PID output exceeds the value of this parameter (which is a percentage of the
reference frequency), a digital output or relay may be congured to provide notication.
LCD Display
Range 0.00 to 100.00% (Default 0.0%)
Description PID low alarm. When PID output falls below the value of this parameter (which is a percentage of the
reference frequency), a digital output or relay may be congured to provide notication.
LCD Display
Range
Parameter Value Description
Disabled (Default) Disables the Sleep Mode function
PID Fback <
The drive goes to sleep (idle) if the feedback is less than the level set in AFN40, set in a percent of full
scale.
PID Fback >
The drive goes to sleep (goes idle) if the feedback is greater than the level set in AFN40 set in a percent
of full scale.
PID Ref <
The drive goes to sleep (goes idle) if the reference is less than the level set in AFN40, set in a percent of
full scale.
PID Ref >
The drive goes to sleep (goes idle) if the reference is greater than the level set in AFN40 set in a percent
of full scale.
z NOTE: Display shows “Zero Speed” when the VFD is in sleep mode