83
Drive Model DRV 22
DRV: Drive Model
22 RSi001S4-1
7 - PARAMETER DESCRIPTION
LCD Display
Description This parameter contains the RSi S4 model number in the format RSihhhS4v, where hhh is the horsepower
rating of the drive and v represents the voltage code.
1 - single phase 120VAC
2 - three-phase 240VAC
4 - three-phase 460VAC
6 - three-phase 600VAC
Jump Code FUN 00
Nom Mtr Volt FUN 01
FUN: Jump Code
00 21
FUN: Nom Mtr Volt
01 230 V
7.1.2 FUN Group
LCD Display
Description By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter
within the group.
LCD Display
Range 100 – 690 Volts (Default is model dependant)
Description This parameter congures the voltage delivered to the motor terminals by the drive at the eld weakening
point (100% motor speed). The eld weakening point is dened in AFN 01 - Nom Mtr Freq on page 111.
z NOTE: Incorrectly setting this parameter will affect motor torque and heating.